Pool

Indoor Pool Dehumidification
Summary of Critical Design Parameters

– Design temperature approximately 2 higher than water temperature
– Design relative humidity 40-60%
– 4-8 Air changes/hour
– Design space pressure slightly negative
– Design 0.5 CFM/sq. ft. deck and pool area
– “Wash” exterior walls and windows with supplied conditioned air
– Introduction of fresh air, in a controlled manner, will positively control indoor pool humidity when it is most important:
WHEN IT IS COLD OUT and when building structures are coldest and most susceptible for condensation formation

Key Advantages

– Increased fresh air (12500 CFM)
– Lower compressor run time (off 75% of the time)
– Better construction
– Lower corrosion issues
– Compressors isolated from pool air
– More reliable with lower cost to operate
– Mfg. and service close
– Higher capacity when cold out (most important during cold outside conditions)

IAQ
Text to come.

Product Guide
Text to come.

Efficiency HCU/Mech
Text to come.